Power Factor Calculator


kW
A
V
Hz
kVA
kVAR
µF

Calculate power factor, apparent power, reactive power, and correction capacitor's capacitance.

The power factor correction capacitor should be connected in parallel to each phase load.

The power factor calculation does not distinguish between leading and lagging power factors.

The power factor correction calculation assumes an inductive load.

Single-phase circuit calculation

Power factor calculation:

PF = |cos φ| = 1000 × P(kW) / (V(V) × I(A))

Apparent power calculation:

|S(kVA)| = V(V) × I(A) / 1000

Reactive power calculation:

Q(kVAR) = √(|S(kVA)|^2 - P(kW)^2)

Power factor correction capacitor's capacitance calculation:

S_corrected(kVA) = P(kW) / PF_corrected

Q_corrected(kVAR) = √(S_corrected(kVA)^2 - P(kW)^2)

Q_c(kVAR) = Q(kVAR) - Q_corrected(kVAR)

C(F) = 1000 × Q_c(kVAR) / (2πf(Hz) × V(V)^2)

Three-phase circuit calculation

For three phases with balanced loads:

Calculation with line-to-line voltage

Power factor calculation:

PF = |cos φ| = 1000 × P(kW) / (3 × VL-L(V) × I(A))

Apparent power calculation:

|S(kVA)| = 3 × VL-L(V) × I(A) / 1000

Reactive power calculation:

Q(kVAR) = √(|S(kVA)|2 - P(kW)2)

Power factor correction capacitor's capacitance calculation:

Qc (kVAR) = Q(kVAR) - Qcorrected (kVAR)

C(F) = 1000 × Qc (kVAR) / (2πf(Hz)×VL-L(V)2)

Calculation with a line to neutral voltage

Power factor calculation:

PF = |cos φ| = 1000 × P(kW) / (3 × VL-N(V) × I(A))

Apparent power calculation:

|S(kVA)| = 3 × VL-N(V) × I(A) / 1000

Reactive power calculation:

Q(kVAR) = √(|S(kVA)|2 - P(kW)2)

Power factor correction capacitor's capacitance calculation:

Qc (kVAR) = Q(kVAR) - Qcorrected (kVAR)

C(F) = 1000 × Qc (kVAR) / (3×2πf(Hz)×VL-N(V)2)